|
Installation
and Configuration Instructions
Note:
This document applies to CheckUPS II Advanced for Novell NetWare
version 3.3 and above only.
Introduction
CheckUPS
II Advanced for Novell NetWare monitors the status of a serially
connected UPS, a remote UPS through a network connection with
a CheckUPS II Data Server, or a UPS being managed by a BestLink
SNMP/WEB Adapter.
During
an extended power failure, the CheckUPS II Advanced may alert
users that are logged into the server, log UPS-related events
to a log file and if necessary, shut down the NetWare operating
system before the UPS reaches a critical, low battery condition.
CheckUPS
II Advanced for Novell NetWare only monitors UPS models with
Advanced (RS-232 communications) only. For those UPS models
that only have Basic communications (relay contacts), Best
Power provides CheckUPS II Basic software for Novell NetWare.
This software may be downloaded from www.bestpower.com.
For
BestLink SNMP/WEB Adapter users, CheckUPS II Advanced for
Novell NetWare also incorporates the shutdown client functionality
required for BestLink to control the shutdown of one or more
NetWare servers during an extended power failure. NetWatch
client software is available separately for those other operating
systems (Windows 9x, NT/2000 and UNIX) that also need to be
shutdown automatically by a BestLink SNMP/WEB Adapter.
This
CheckUPS software is compatible with Novell NetWare versions
3.20, 4.1x and 5.x.
Note:
NetWare 3.20 users should read the requirements
notes below before running the CheckUPS II Advanced NLM.
As
you progress through the configuration of the CheckUPS II
Advanced software for Novell NetWare, be advised that all
configuration updates are applied to the main CheckUPS Configuration
display. Due to the nature of the NetWare screen interface,
they will not be displayed on any overlay windows that are
open as they cannot be updated dynamically.
Special
NetWare 3.20 Requirements
Below
are important notes about additional software required on
your NetWare 3.20 server for use with the CheckUPS II Advanced
NLM.
CLIBAUX.NLM
must be loaded before loading CHECKUPS.NLM. If CLIBAUX.NLM
is not in your SYS:\SYSTEM directory, go to http://support.novell.com/misc/patlst.htm,
and then download and install the Netware 3.2 CLIB update
file "LIB312D.EXE". Modify the AUTOEXEC.NCF file
in SYS:\SYSTEM to include the line "load clibaux",
or load the NLM manually before loading CHECKUPS.NLM.
NETDB.NLM
must be in the SYS:\SYSTEM directory before loading CHECKUPS.NLM.
If NETDB.NLM is not present on your system, go to http://support.novell.com
and search for "NIP22B.EXE". Download this file
to a temp directory, and then double-click on it to extract
the contents. You do not have to install NetWare IP, simply
copy NETDB.NLM from the "dhcp\dhcpsrvr\utils\3x"
directory to the SYS:\SYSTEM directory of your server.
After
the above steps are completed, CHECKUPS.NLM can be loaded.
Preparation
Before
configuring the software for use, it is assumed that you ran
the supplied installation software (chkadnov.exe) from a Windows
PC, which copied the specific NLMs and supporting files to
SYS:SYSTEM on your NetWare server.
Please
note that language files are also copied to your NetWare server,
so if you run your NetWare server in a language other than
English (i.e., French, German, Spanish, Italian or Portuguese),
CheckUPS will run using the selected language.
Make
sure the UPS protecting your server is powered up and the
supplied communications cable (INT-0062 or INT-0035) is connected
between the BestPort (DB9 or DB25 connection) on the UPS and
a free serial connection on your server.
If
a different server (running a copy of the CheckUPS II Data
Server software) is to have a serial connection to the UPS,
make sure the cable is in place and the software is configured
and running on that server. Likewise, if a BestLink SNMP/WEB
Adapter is monitoring the UPS, make sure it is configured
and running before starting to configure CheckUPS II Advanced
on this server.
Starting
the Software
As
administrator of your NetWare server, gain access to the SYS:SYSTEM
directory and type the following to start the CheckUPS II
Advanced software:
load
checkups
Note:
In version 3.35 and later of this software, a feature was
added that allows you to type load checkups -d to force the
software to reset its configuration to default. This should
be used in cases where you have reconfigured your UPS environment
and want to reconfigure the software. Running the software
without forcing it to default conditions, when the UPS and/or
network has changed, will result in the software attempting
to run based on what it knew of the previous environment.
A
Monitoring Options selection
box will be displayed containing the following choices:
Local
UPS
Remote
UPS
BestLink
SNMP/WEB Adapter
Reset
Defaults
Exit
For
users with UPS models capable of Advanced communications, CheckUPS
II Advanced for Novell NetWare provides the user with software
capable of being used in several scenarios. Please review the
scenarios below to better understand how to configure and use
the software on your server. Each scenario refers you to the
Monitoring Option that
you need to select to correctly configure the NLM.
Possible
Scenarios:
UPS
monitoring to be done by a NetWare server connected locally
(via RS-232) to its UPS, where additional, networked servers
and/or workstations need to monitor the same UPS remotely (via
TCP/IP).
Select
Local UPS as the Monitoring Option
that matches this scenario, since this requires you to configure
the CheckUPS II Advance NLM for Serial communications with
a UPS attached directly to the server and configure the
Remote Data Server functionality to provide UPS data to
other clients via the network.
Remember
that the Scenario you chose is number 1.
UPS
monitoring to be done by a NetWare server connected remotely
(via TCP/IP) to a separate server or workstation running CheckUPS
II Data Server software (NetWare, NT/2000 or UNIX version).
Select
Remote UPS as the Monitoring Option
that matches this scenario, since this requires you to configure
the CheckUPS II Advance NLM for Remote (network) communications
with copy of the CheckUPS II Data Server (NT/2000, NetWare
or UNIX) running on a remote server.
Remember
that the Scenario you chose is number 2.
UPS
monitoring to be done by a single NetWare server connected
locally (via RS-232) to its UPS (This is different from Scenario
1 because no remote monitoring is possible by other servers
or workstations because the integral Data Server is not started).
Select
Local UPS as the Monitoring Option
that matches this scenario, since this requires you to configure
the CheckUPS II Advanced NLM for Serial communications with
a UPS attached directly to the server. Note that not other
CheckUPS client software will be able to obtain UPS data
from the CheckUPS software configured in this manner.
Remember
that the Scenario you chose is number 3.
UPS
monitoring by a single NetWare server connected remotely (via
TCP/IP) to a UPS being controlled by a BestLink SNMP/WEB Adapter.
Select
BestLink SNMP/WEB Adapter
as the Monitoring Option that matches this scenario, since
this requires you to configure the CheckUPS II Advanced
NLM to act as a shutdown client when communicating with
an active BestLink SNMP/WEB Adapter.
Remember
that the Scenario you chose is number 4.
Make
the selection that applies to your environment and then continue
with the appropriate section (below) based on the Monitoring
Option you selected. If you need
to reset the program to its factory defaults, select
Reset Defaults.
Local
UPS
Upon
selecting
Local UPS as the
Monitoring Option, you
will then be presented with the following CheckUPS
Options:
Monitor
UPS only
Monitor
UPS and Start Remote Data Server
Use
Current CheckUPS Configuration
Exit
If
you chose Scenario 1, then select
Monitor
UPS and Start Remote Data Server.
If
you chose Scenario 3, then select
Monitor UPS only.
If
you previously configured CheckUPS II then select Use Current
CheckUPS Configuration to continue with those settings.
After
making the appropriate CheckUPS Options selection as listed
above, continue with the text that matches that selection
below. If you desire to Exit the current selection screen,
select Exit.
Monitor
UPS only
Upon
selecting Monitor UPS only, you will then be presented with
the following
Configuration Options:
Current
UPS COM Port: COM2
Discover
Available COM Ports
Current
UPS: None
Detect
UPS
Start
Monitoring
Exit
To
begin monitoring the UPS, follow the steps listed below:
- Select
Discover Available COM Ports which
will present you with a list of available COM ports on your
NetWare server. It displays all serial ports from which you
can select the one the UPS is connected to.
- Select
Detect UPS to
instruct CheckUPS to attempt communications with the UPS connected
to the COM port you selected. If your are presented with the
message
>Error: Invalid COM Port <Press ENTER to continue>
then the COM port you selected is most
likely connected to something other than a UPS. Upon detecting
a UPS, the software then automatically identifies the UPS
model. This may take several seconds. Upon the successful
detection, the name of the UPS model being monitored is displayed
as the Current Detected UPS. Press
Enter to remove the
display box from the screen. Failure to detect and identify
the UPS may indicate a communications port problem. Do not
proceed until the problem is rectified.
- Finally,
select
Start Monitoring which
instructs CheckUPS to start communicating with the detected
UPS.
Once
communications has been established with the UPS, the CheckUPS
II Advanced main screen is updated, showing the current CheckUPS
Configuration and the current status of the UPS being monitored.
Proceed
by configuring CheckUPS to correctly handle UPS-related events,
including possible operating system shutdown. To do so, press
the
F8 key for more options.
Upon
doing so, you will be presented with the following options:
Edit
Configuration
View
Event Log
View
Event Log File
Stop
Monitoring
Exit
Select
Edit Configuration and
continue with the following.
Operating
System Shutdown Options:
There
are four shutdown options to choose from. They are:
- Operating
System Shutdown Disabled
- Start
Shutdown after Operating on Battery for 5 min (Default)
- Start
Shutdown only on UPS-Reported Low Battery Alarm
- Start
Shutdown when Battery Runtime Reaches 5 min
Selecting
the current shutdown option and pressing the Enter key displays
the four choices (in alphabetical order as shown above). Once
you make a new selection, CheckUPS requires that you provide
any timing value associated with that choice. The shutdown
options are explained in detail below.
Operating
System Shutdown Disabled
By
default, this selection is disabled. If a power failure
occurs and the UPS runs out of battery runtime, the UPS
will turn off. If you select this option, the server will
not be properly shut down.
Start
Shutdown after Operating on Battery for 5 min (Default)
By
default, this selection is enabled. This allows the CheckUPS
II Advanced NLM to start the automatic shutdown of the NetWare
server at a specific amount of time following the start
of a power failure.
The
user is allowed to select a length of Power Failure value
(m) from 1 to 99 minutes, with the default being 5 minutes.
The
value you choose instructs CheckUPS II to wait m minutes
after the start (and continuation) of a power failure before
starting the automatic shutdown of the NetWare server.
Please
note that the occurrence of a UPS-generated Low Battery
Alarm before the length of the power failure reaches the
number of minutes selected, causes the start of an immediate
shutdown.
Start
Shutdown only on UPS-Reported Low Battery Alarm
By
default, this selection is disabled. However, it is available
whether your UPS calculates Battery Runtime remaining or
not. By enabling this selection, you can instruct the CheckUPS
II Advanced NLM to only start the automatic shutdown of
the NetWare server whenever a UPS-generated Low Battery
Alarm occurs.
Start
Shutdown when Battery Runtime Reaches 5 min
By
default, this selection is disabled. However, if the UPS
to be monitored calculates Battery Runtime remaining, the
user may choose this selection to allow the UPS-protected
systems to run as long as possible before the automatic
shutdown starts. For UPS models that do not calculate Battery
Runtime remaining, this selection cannot be enabled.
Upon
selecting this option, the user is required to select a
Battery Runtime remaining value (n) from 3 to 99 minutes,
with the default being 5 minutes.
The
value you choose instructs CheckUPS to wait until n minutes
of available Battery Runtime to start the automatic shutdown
of the NetWare server - only during a power failure condition.
Please
note that the occurrence of a UPS-generated Low Battery
Alarm before the amount of Battery Runtime remaining you
choose is reached, causes the start of an immediate shutdown.
Minutes
Required for Operating System Shutdown (Default: 2)
The
user must set the time required to complete the NetWare
Operating System Shutdown from 1 to 60 minutes, but must
be conscious of the other numerical settings to ensure enough
time is allowed for the system to complete its shutdown
prior to the UPS running out of battery runtime.
Execute
Batch File prior to Operating System Shutdown (Default: No)
If
you need to run a batch file prior to the actual NetWare shutdown,
you may instruct CheckUPS to do so.
To
change the value, press Y for Yes or N for No, followed by
pressing
Enter.
Minutes
Required for Batch File Execution (Default: 1)
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must instruct CheckUPS how long it needs to
wait for the batch file to complete its execution.
This
time can range from 1 to 60 minutes, but the user must be
conscious of the other numerical settings to ensure enough
time is allowed for the system to complete its shutdown
prior to the UPS running out of battery runtime.
To
change the numerical value, press Enter to select the setting.
Then type in the number of minutes required, followed by
pressing Enter again to accept the setting.
Batch
File Name: SYS:SYSTEM\UPSDOWN.NCF
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must tell CheckUPS the path and filename of
the batch file (.ncf file) to be executed.
To
change the path and filename, press Enter to select the
setting. Then type in the new path and filename or edit
the current one. Press Enter to accept the new setting.
Edit
Batch File SYS:SYSTEM\UPSDOWN.NCF
Pressing
Enter to select this setting, allows the user to edit the
actual batch file from within CheckUPS.
Enable
Event Logging (Default: Yes)
By
default, UPS-related events are logged into the file SYS:SYSTEM\CHECKUPS.LOG.
You may instruct CheckUPS not to log the events as they
happened, but this is not recommended.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Enable
Event Message Broadcasting (Default: No)
By
default, UPS-related events are broadcast as messages to
logged-in users. In most cases it is desirable to keep users
informed as UPS-related events take place.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Start
Monitoring when NLM is loaded (Default: No)
Once
you successfully establish communications with a UPS, CheckUPS
automatically updates this setting to Yes. By doing so,
CheckUPS will start monitoring each time the CheckUPS NLM
is loaded.
F8
key Options continued
View
Event Log
Select
View Event Log to allow you to scroll up or down in the
Event Log found at the bottom of the CheckUPS II Advanced
main screen. The up and down arrow keys found on your keyboard
will then be active. Press the Esc key to exit the log.
View
Event Log File
Select
View Event Log File to allow you to view the physical CheckUPS
log file found at SYS:SYSTEM\CHECKUPS.LOG. All four arrow
keys found on your keyboard will then be active. Press the
Esc key to exit the log.
Stop
Monitoring
Select
Stop
Monitoring to instruct CheckUPS to
discontinue monitoring the UPS in the current manner. This
is useful during initial testing, but should be used with
caution since no UPS monitoring or automatic shutdown functionality
will be active if monitoring has been discontinued.
Exit
Selecting
Exit is like pressing the Esc key.
It removes the currently displayed menu window from your
screen, returning you to the previous display.
Your
CheckUPS II Advanced software for NetWare is now configured
based on the scenario you selected.
Monitor
UPS and Start Remote Data Server
Upon
selecting
Monitor UPS and Start Remote Data Server, you
will then be presented with the following Configuration
Options:
Current
UDP Listen Port Value: 2844
Edit
UDP Listen Port Value
Current
UPS COM Port: COM2
Discover
Available COM Ports
Current
UPS: None
Detect
UPS
Start
Monitoring
Exit
To
begin monitoring the UPS, follow the steps listed below:
- The
default
UDP Listen Port Value that
the Remote Data Server portion of CheckUPS uses to honor
requests for UPS data from remote CheckUPS clients is 2844.
Although you are allowed to change this port number by selecting
Edit UPS Listen Port Value, it
is not recommended. 2844 has been assigned specifically
to Best Power by IANA.
- Select
Discover
Available COM Ports which
will present you with a list of available COM ports on your
NetWare server. It displays all serial ports from which
you can select the one the UPS is connected to.
- Select
Detect UPS to instruct CheckUPS to attempt
communications with the UPS connected to the COM port you
selected. If your are presented with the message
Error: Invalid COM Port <Press ENTER to continue>
then the COM port you selected is
most likely connected to something other than a UPS. Upon
detecting a UPS, the software then automatically identifies
the UPS model. This may take several seconds. Upon the successful
detection, the name of the UPS model being monitored is
displayed as the Current Detected UPS.
Press Enter to
remove the display box from the screen. Failure to detect
and identify the UPS may indicate a communications port
problem. Do not proceed until the problem is rectified.
- Finally,
select Start
Monitoring which instructs
CheckUPS to start communicating with the detected UPS and
allows it to make that UPS data available to other CheckUPS
II Advanced client software.
Once
communications has been established with the UPS, the CheckUPS
II Advanced main screen is updated, showing the current CheckUPS
Configuration and the current status of the UPS being monitored.
Proceed
by configuring CheckUPS to correctly handle UPS-related events,
including possible operating system shutdown. To do so, press
the
F8 key for more options.
Upon
doing so, you will be presented with the following options:
Edit
Configuration
View
Event Log
View
Event Log File
Stop
Monitoring
Exit
Select
Edit Configuration and
continue with the following.
Operating
System Shutdown Options:
There
are four shutdown options to choose from. They are:
- Operating
System Shutdown Disabled
- Start
Shutdown after Operating on Battery for 5 min (Default)
- Start
Shutdown only on UPS-Reported Low Battery Alarm
- Start
Shutdown when Battery Runtime Reaches 5 min
Selecting
the current shutdown option and pressing the Enter key displays
the four choices (in alphabetical order as shown above). Once
you make a new selection, CheckUPS requires that you provide
any timing value associated with that choice. The shutdown
options are explained in detail below.
Operating
System Shutdown Disabled
By
default, this selection is disabled. If a power failure
occurs and the UPS runs out of battery runtime, the UPS
will turn off. If you select this option, the server will
not be properly shut down.
Start
Shutdown after Operating on Battery for 5 min (Default)
By
default, this selection is enabled. This allows the CheckUPS
II Advanced NLM to start the automatic shutdown of the NetWare
server at a specific amount of time following the start
of a power failure.
The
user is allowed to select a length of Power Failure value
(m) from 1 to 99 minutes, with the default being 5 minutes.
The
value you choose instructs CheckUPS to wait m minutes after
the start (and continuation) of a power failure before starting
the automatic shutdown of the NetWare server.
Please
note that the occurrence of a UPS-generated Low Battery
Alarm before the length of the power failure reaches the
number of minutes selected, causes the start of an immediate
shutdown.
If
you have other CheckUPS II Advanced clients that obtain
their UPS data from the Data Server function in CheckUPS
running on this NetWare server, then in most cases they
should all have the same shutdown settings. However, you
may choose to set some to a smaller Operating on Battery
value to conserve battery runtime for more important systems.
The system running the CheckUPS II Data Server should be
the last system to start its shutdown in all cases and should
have the largest (longest) value for the Operating on Battery
value.
Start
Shutdown only on UPS-Reported Low Battery Alarm
By
default, this selection is disabled. However, it is available
whether your UPS calculates Battery Runtime remaining or
not. By enabling this selection, you can instruct the CheckUPS
II Advanced NLM to only start the automatic shutdown of
the NetWare server whenever a UPS-generated Low Battery
Alarm occurs.
Start
Shutdown when Battery Runtime Reaches 5 min
By
default, this selection is disabled. However, if the UPS
to be monitored calculates Battery Runtime remaining, the
user may choose this selection to allow the UPS-protected
systems to run as long as possible before the automatic
shutdown starts. For UPS models that do not calculate Battery
Runtime remaining, this selection cannot be enabled.
Upon
selecting this option, the user is required to select a
Battery Runtime remaining value (n) from 3 to 99 minutes,
with the default being 5 minutes.
The
value you choose instructs CheckUPS II to wait until n minutes
of available Battery Runtime to start the automatic shutdown
of the NetWare server - only during a power failure condition.
Please
note that the occurrence of a UPS-generated Low Battery
Alarm before the amount of Battery Runtime remaining you
choose is reached, causes the start of an immediate shutdown.
If
you have other CheckUPS II Advanced clients that obtain
their UPS data from the Data Server function in CheckUPS
running on this NetWare server, then in most cases they
should all have the same shutdown settings. However, you
may choose to set some to a larger Battery Runtime remaining
value to conserve Battery Runtime for more important systems.
The system running the CheckUPS II Data Server should be
the last system to start its shutdown in all cases and should
have the smallest value for the Battery Runtime remaining.
Minutes
Required for Operating System Shutdown (Default: 2)
The
user must set the time required to complete the NetWare
Operating System Shutdown from 1 to 60 minutes, but must
be conscious of the other numerical settings to ensure enough
time is allowed for the system to complete its shutdown
prior to the UPS running out of battery runtime.
Execute
Batch File prior to Operating System Shutdown (Default:
No)
If
you need to run a batch file prior to the actual NetWare
shutdown, you may instruct CheckUPS to do so.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Minutes
Required for Batch File Execution (Default: 1)
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must instruct CheckUPS how long it needs to
wait for the batch file to complete its execution.
This
time can range from 1 to 60 minutes, but the user must be
conscious of the other numerical settings to ensure enough
time is allowed for the system to complete its shutdown
prior to the UPS running out of battery runtime.
To
change the numerical value, press Enter to select the setting.
Then type in the number of minutes required, followed by
pressing Enter again to accept the setting.
Batch
File Name: SYS:SYSTEM\UPSDOWN.NCF
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must tell CheckUPS the path and filename of
the batch file (.ncf file) to be executed.
To
change the path and filename, press Enter to select the
setting. Then type in the new path and filename or edit
the current one. Press Enter to accept the new setting.
Edit
Batch File SYS:SYSTEM\UPSDOWN.NCF
Pressing
Enter to select this setting, allows the user to edit the
actual batch file from within CheckUPS.
Enable
Event Logging (Default: Yes)
By
default, UPS-related events are logged into the file SYS:SYSTEM\CHECKUPS.LOG.
You may instruct CheckUPS not to log the events as they
happened, but this is not recommended.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Enable
Event Message Broadcasting (Default: No)
By
default, UPS-related events are broadcast as messages to
logged-in users. In most cases it is desirable to keep users
informed as UPS-related events take place.
To
change the value, press Y for Yes or N for No, followed
by pressing
Enter.
Start
Monitoring when NLM is loaded (Default: No)
Once
you successfully establish communications with a UPS, CheckUPS
automatically updates this setting to Yes. By doing so,
CheckUPS will start monitoring each time the CheckUPS NLM
is loaded.
F8
key Options continued
View
Event Log
Select
View Event Log to allow you to scroll up or down in the
Event Log found at the bottom of the CheckUPS II Advanced
main screen. The up and down arrow keys found on your keyboard
will then be active. Press the Esc key to exit the log.
View
Event Log File
Select
View Event Log File to allow you to view the physical CheckUPS
log file found at SYS:SYSTEM\CHECKUPS.LOG. All four arrow
keys found on your keyboard will then be active. Press the
Esc key to exit the log.
Stop
Monitoring
Select
Stop Monitoring to instruct CheckUPS to discontinue monitoring
the UPS in the current manner. This is useful during initial
testing, but should be used with caution since no UPS monitoring
or automatic shutdown functionality will be active if monitoring
has been discontinued.
Exit
Selecting
Exit is like pressing the Esc key. It removes the currently
displayed menu window from your screen, returning you to
the previous display.
Your
CheckUPS II Advanced software for NetWare is now configured
based on the scenario you selected.
Remote
UPS
If
you chose Scenario 2 because the NetWare server will connect
remotely to a separate system running CheckUPS II Data Server
software, in order to obtain UPS data, then continue with this
section.
Upon
selecting
Remote UPS as the
Monitoring Option, you
will then be presented with the following Remote
Server Options:
Current
UDP Target Port Value: 2844
Edit
UDP Target Port Value
Discover
all Remote Servers
Enter
Remote Server IP Address or Hostname
Use Current
Remote Server Configuration
Exit
To
begin monitoring the UPS, follow the steps listed below:
- The
default Current
UDP Target Port Value that
CheckUPS uses to request UPS data from remote servers is
2844. Although you are allowed to change this port number
by selecting Edit UDP Target Port Value,
it is not recommended. 2844 has been
assigned specifically to Best Power by IANA.
- Select
Discover
all Remote Servers to instruct
CheckUPS to attempt to locate any CheckUPS II Data Servers
on your network. Upon doing so, CheckUPS will present a
Remote Servers list
from which you can select the Hostname or IP Address of
the Remote Server you wish to obtain your UPS data from.
Typically, you would pick the one that is being protected
by the UPS that provides power to the NetWare server you
are currently configuring CheckUPS software for. Selecting
a valid Hostname or IP Address from the list and pressing
Enter starts the communications process with the remote
server.
- If
for some reason, the remote server you wish to use is not
listed, then you may enter the IP Address or Hostname of
the remote server manually by selecting
Enter Remote Server IP Address or Hostname.
Upon entering the valid IP Address
or Hostname, the communications process with the remote
server will be started.
Once
communications has been established with the remote CheckUPS
II Data Server, the CheckUPS II Advanced main screen is updated,
showing the current CheckUPS Configuration and the current status
of the UPS being monitored.
Proceed
by configuring CheckUPS to correctly handle UPS-related events,
including possible operating system shutdown. To do so, press
the
F8 key for more options.
Upon
doing so, you will be presented with the following options:
Edit
Configuration
View
Event Log
View
Event Log File
Stop
Monitoring
Exit
Select
Edit Configuration and
continue with the following.
Operating
System Shutdown Options:
There
are four shutdown options to choose from. They are:
- Operating
System Shutdown Disabled
- Start
Shutdown after Operating on Battery for 5 min (Default)
- Start
Shutdown only on UPS-Reported Low Battery Alarm
- Start
Shutdown when Battery Runtime Reaches 5 min
Selecting
the current shutdown option and pressing the Enter key displays
the four choices (in alphabetical order as shown above). Once
you make a new selection, CheckUPS requires that you provide
any timing value associated with that choice. The shutdown
options are explained in detail below.
Operating
System Shutdown Disabled
By
default, this selection is disabled. If a power failure
occurs and the UPS runs out of battery runtime, the UPS
will turn off. If you select this option, the server will
not be properly shut down.
Start
Shutdown after Operating on Battery for 5 min (Default)
By
default, this selection is enabled. This allows the CheckUPS
II Advanced NLM to start the automatic shutdown of the NetWare
server at a specific amount of time following the start
of a power failure.
The
user is allowed to select a length of Power Failure value
(m) from 1 to 99 minutes, with the default being 5 minutes.
The
value you choose instructs CheckUPS to wait m minutes after
the start (and continuation) of a power failure before starting
the automatic shutdown of the NetWare server.
Please
note that the occurrence of a UPS-generated Low Battery
Alarm before the length of the power failure reaches the
number of minutes selected, causes the start of an immediate
shutdown.
If
you have other CheckUPS II Advanced clients that obtain
their UPS data from the Data Server function in CheckUPS
running on this NetWare server, then in most cases they
should all have the same shutdown settings. However, you
may choose to set some to a smaller Operating on Battery
value to conserve battery runtime for more important systems.
The system running the CheckUPS II Data Server should be
the last system to start its shutdown in all cases and should
have the largest (longest) value for the Operating on Battery
value.
Start
Shutdown only on UPS-Reported Low Battery Alarm
By
default, this selection is disabled. However, it is available
whether your UPS calculates Battery Runtime remaining or
not. By enabling this selection, you can instruct the CheckUPS
II Advanced NLM to only start the automatic shutdown of
the NetWare server whenever a UPS-generated Low Battery
Alarm occurs.
Start
Shutdown when Battery Runtime Reaches 5 min
By
default, this selection is disabled. However, if the UPS
to be monitored calculates Battery Runtime remaining, the
user may choose this selection to allow the UPS-protected
systems to run as long as possible before the automatic
shutdown starts. For UPS models that do not calculate Battery
Runtime remaining, this selection cannot be enabled.
Upon
selecting this option, the user is required to select a
Battery Runtime remaining value (n) from 3 to 99 minutes,
with the default being 5 minutes.
The
value you choose instructs CheckUPS to wait until n minutes
of available Battery Runtime to start the automatic shutdown
of the NetWare server - only during a power failure condition.
Please
note that the occurrence of a UPS-generated Low Battery
Alarm before the amount of Battery Runtime remaining you
choose is reached, causes the start of an immediate shutdown.
If
you have other CheckUPS II Advanced clients that obtain
their UPS data from the Data Server function in CheckUPS
running on this NetWare server, then in most cases they
should all have the same shutdown settings. However, you
may choose to set some to a larger Battery Runtime remaining
value to conserve Battery Runtime for more important systems.
The system running the CheckUPS II Data Server should be
the last system to start its shutdown in all cases and should
have the smallest value for the Battery Runtime remaining.
Minutes
Required for Operating System Shutdown (Default: 2)
The
user must set the time required to complete the NetWare
Operating System Shutdown from 1 to 60 minutes, but must
be conscious of the other numerical settings to ensure enough
time is allowed for the system to complete its shutdown
prior to the UPS running out of battery runtime.
Execute
Batch File prior to Operating System Shutdown (Default: No)
If
you need to run a batch file prior to the actual NetWare
shutdown, you may instruct CheckUPS to do so.
To
change the value, press Y
for Yes or N for
No, followed by pressing Enter.
Minutes
Required for Batch File Execution (Default: 1)
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must instruct CheckUPS how long it needs to
wait for the batch file to complete its execution.
This
time can range from 1 to 60 minutes, but the user must be
conscious of the other numerical settings to ensure enough
time is allowed for the system to complete its shutdown
prior to the UPS running out of battery runtime.
To
change the numerical value, press Enter to select the setting.
Then type in the number of minutes required, followed by
pressing Enter again to accept the setting.
Batch
File Name: SYS:SYSTEM\UPSDOWN.NCF
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must tell CheckUPS the path and filename of
the batch file (.ncf file) to be executed.
To
change the path and filename, press Enter to select the
setting. Then type in the new path and filename or edit
the current one. Press Enter to accept the new setting.
Edit
Batch File SYS:SYSTEM\UPSDOWN.NCF
Pressing
Enter to select this setting, allows the user to edit the
actual batch file from within CheckUPS.
Enable
Event Logging (Default: Yes)
By
default, UPS-related events are logged into the file SYS:SYSTEM\CHECKUPS.LOG.
You may instruct CheckUPS not to log the events as they
happened, but this is not recommended.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Enable
Event Message Broadcasting (Default: No)
By
default, UPS-related events are broadcast as messages to
logged-in users. In most cases it is desirable to keep users
informed as UPS-related events take place.
To
change the value, press
Y for Yes or N for
No, followed by pressing Enter.
Start
Monitoring when NLM is loaded (Default: No)
Once
you successfully establish communications with a remote
CheckUPS II Data Server, CheckUPS automatically updates
this setting to Yes. By doing so, CheckUPS will start monitoring
each time the CheckUPS NLM is loaded.
F8
key Options continued
View
Event Log
Select
View Event Log to allow you to scroll
up or down in the Event Log found at the bottom of the CheckUPS
II Advanced main screen. The up and down arrow keys found
on your keyboard will then be active. Press the Esc
key to exit the log.
View
Event Log File
Select
View
Event Log File to allow you to view
the physical CheckUPS log file found at SYS:SYSTEM\CHECKUPS.LOG.
All four arrow keys found on your keyboard will then be
active. Press the Esc key to
exit the log.
Stop
Monitoring
Select
Stop
Monitoring to instruct CheckUPS to
discontinue monitoring the UPS in the current manner. This
is useful during initial testing, but should be used with
caution since no UPS monitoring or automatic shutdown functionality
will be active if monitoring has been discontinued.
Exit
Selecting
Exit is like pressing the Esc
key. It removes the currently displayed
menu window from your screen, returning you to the previous
display.
Your
CheckUPS II Advanced software for NetWare is now configured
based on the scenario you selected.
BestLink
SNMP/WEB Adapter
If
you chose Scenario 4 because the NetWare server will connect
remotely to a BestLink SNMP/WEB Adapter to obtain UPS status
data, then continue with this section.
Upon
selecting
BestLink SNMP/WEB Adapter as
the Monitoring Option,
you will then be presented with the following BestLink
Options:
Discover
BestLink SNMP/WEB Adapters
Enter
BestLink IP Address or Hostname
Use Current
BestLink Configuration
Exit
To
begin monitoring the UPS, follow the steps listed below:
- Select
Discover BestLink SNMP/WEB
Adapters to instruct CheckUPS to attempt
to locate any BestLink SNMP/WEB Adapters on your network.
Upon doing so, CheckUPS will present a
BestLink SNMP/WEB Adapters list
from which you can select the IP Address (or Hostname) of
the BestLink you wish to obtain your UPS status data from.
Typically, you would pick the one that is monitoring the
UPS that provides power to the NetWare server you are currently
configuring CheckUPS software for. Selecting a valid IP
Address from the list and pressing Enter starts the communications
process with the BestLink SNMP/WEB Adapter.
- If
for some reason, the BestLink SNMP/WEB Adapter you wish
to monitor is not listed, then you may enter its IP Address
or Hostname manually by selecting
Enter BestLink IP Address or Hostname.
Upon entering the valid IP Address or Hostname, the communications
process with the BestLink SNMP/WEB Adapter will be started.
Once
communications has been established with the BestLink SNMP/WEB
Adapter to be monitored, the CheckUPS II Advanced main screen
is updated, showing the current BestLink (monitoring) Configuration
and the current (simple) status of the UPS being monitored.
Proceed
by configuring CheckUPS to correctly handle UPS-related events,
including possible operating system shutdown. To do so, press
the F8 key for more options.
Upon
doing so, you will be presented with the following options:
Edit
Configuration
View
Event Log
View
Event Log File
Stop
Monitoring
Exit
Select
Edit Configuration and
continue with the following.
Operating
System Shutdown Options:
There
are four shutdown options to choose from. They are:
- Operating
System Shutdown Disabled
- Start
Shutdown after Operating on Battery for 5 min (Default)
- Start
Shutdown only on UPS-Reported Low Battery Alarm
- Start
Shutdown when Battery Runtime Reaches 5 min
Selecting
the current shutdown option and pressing the Enter key displays
the four choices (in alphabetical order as shown above). Once
you make a new selection, CheckUPS requires that you provide
any timing value associated with that choice. The shutdown
options are explained in detail below.
Operating
System Shutdown Disabled
By
default, this selection is disabled. If a power failure
occurs and the UPS runs out of battery runtime, the UPS
will turn off. If you select this option, the server will
not be properly shut down.
Start
Shutdown after Operating on Battery for 5 min (Default)
By
default, this selection is enabled. This allows the CheckUPS
II Advanced NLM to start the automatic shutdown of the NetWare
server at a specific amount of time following the start
of a power failure as reported by the BestLink SNMP/WEB
Adapter.
The
user is allowed to select a length of Power Failure value
(m) from 1 to 99 minutes, with the default being 5 minutes.
The
value you choose instructs CheckUPS to wait m minutes after
the start (and continuation) of a power failure before starting
the automatic shutdown of the NetWare server.
Please
note that the occurrence of a UPS-generated, BestLink-reported
Low Battery Alarm before the length of the power failure
reaches the number of minutes selected, causes the start
of an immediate shutdown.
Start
Shutdown only on UPS-Reported Low Battery Alarm
By
default, this selection is disabled. However, it is available
whether your UPS calculates Battery Runtime remaining or
not. By enabling this selection, you can instruct the CheckUPS
II Advanced NLM to only start the automatic shutdown of
the NetWare server whenever a UPS-generated, BestLink-reported
Low Battery Alarm occurs.
Start
Shutdown when Battery Runtime Reaches 5 min
By
default, this selection is disabled. However, if the UPS
to be monitored calculates Battery Runtime remaining, the
user may choose this selection to allow the UPS-protected
systems to run as long as possible before the automatic
shutdown starts. For UPS models that do not calculate Battery
Runtime remaining, this selection cannot be enabled.
Upon
selecting this option, the user is required to select a
Battery Runtime remaining value (n) from 3 to 99 minutes,
with the default being 5 minutes.
The
value you choose instructs CheckUPS to wait until n minutes
of available Battery Runtime to start the automatic shutdown
of the NetWare server - only during a power failure condition.
Please
note that the occurrence of a UPS-generated Low Battery
Alarm before the amount of Battery Runtime remaining you
choose is reached, causes the start of an immediate shutdown.
Execute
Batch File prior to Operating System Shutdown (Default: No)
If
you need to run a batch file prior to the actual NetWare
shutdown, you may instruct CheckUPS to do so.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Minutes
Required for Batch File Execution (Default: 1)
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must instruct CheckUPS how long it needs to
wait for the batch file to complete its execution.
This
time can range from 1 to 60 minutes, but the user must be
conscious of the other numerical settings (specifically
those on the BestLink SNMP/WEB Adapter) to ensure enough
time is allowed for the system to complete its shutdown
prior to the UPS running out of battery runtime or turning
off under the control of the BestLink SNMP/WEB Adapter.
To
change the numerical value, press Enter to select the setting.
Then type in the number of minutes required, followed by
pressing Enter again to accept the setting.
Batch
File Name: SYS:SYSTEM\UPSDOWN.NCF
If
you enable the Execution of a Batch File prior to the NetWare
shutdown, you must tell CheckUPS the path and filename of
the batch file (.ncf file) to be executed.
To
change the path and filename, press Enter to select the
setting. Then type in the new path and filename or edit
the current one. Press Enter to accept the new setting.
Edit
Batch File SYS:SYSTEM\UPSDOWN.NCF
Pressing
Enter to select this setting, allows the user to edit the
actual batch file from within CheckUPS.
Enable
Event Logging (Default: Yes)
By
default, UPS-related events are logged into the file SYS:SYSTEM\CHECKUPS.LOG.
You may instruct CheckUPS not to log the events as they
happened, but this is not recommended.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Enable
Event Message Broadcasting (Default: No)
By
default, UPS-related events are broadcast as messages to
logged-in users. In most cases it is desirable to keep users
informed as UPS-related events take place.
To
change the value, press Y for Yes or N for No, followed
by pressing Enter.
Start
Monitoring when NLM is loaded (Default: No)
Once
you successfully establish communications with a BestLink
SNMP/WEB Adapter, CheckUPS automatically updates this setting
to Yes. By doing so, CheckUPS will start monitoring the
BestLink SNMP/WEB Adapter each time the CheckUPS NLM is
loaded.
F8
key Options continued
View
Event Log
Select
View Event Log to allow you to scroll up or down in the
Event Log found at the bottom of the CheckUPS II Advanced
main screen. The up and down arrow keys found on your keyboard
will then be active. Press the Esc key to exit the log.
View
Event Log File
Select
View Event Log File to allow you to view the physical CheckUPS
log file found at SYS:SYSTEM\CHECKUPS.LOG. All four arrow
keys found on your keyboard will then be active. Press the
Esc key to exit the log.
Stop
Monitoring
Select
Stop Monitoring to instruct CheckUPS to discontinue monitoring
the UPS in the current manner. This is useful during initial
testing, but should be used with caution since no UPS monitoring
or automatic shutdown functionality will be active if monitoring
has been discontinued.
Exit
Selecting
Exit is like pressing the Esc key. It removes the currently
displayed menu window from your screen, returning you to
the previous display.
Your
CheckUPS II Advanced software for NetWare is now configured
based on the scenario you selected.
|